kWh PDU provide advanced and various power information, including voltage, current, frequency, power factor, VA and kWh. It also provide carbon emission data for reference.
Features
Meter: True RMS Current Meter, Voltage, Frequency, Power Factor, Active Power, Apparent Power, Total kWh, Sub-total kWh.
Power Monitor: Total Power Monitoring byMeter, Web, SNMP, Free Bundle Software
Protocols: Http, Https, SNMP, DHCP, UDP
Outlet Control: Individual, Group, Schedule, Auto Ping
Power Delay: Power On/Off Sequence can be Defined
Alarm Thresholds: User-Defined Alarm Thresholds for Warning and Overload
Event Alert: Email, Trap, Audible Alarm
Temp./Humidity: Option Accessory
PDU Diagram
Specification
Model No.
PDUA-KH1511-0801
PDUA-KH1623-0801
Output Socket
(8) NEMA 5-15/20R
(8) IEC320 C13
Input Socket
(1) IEC320 C20
(1) IEC320 C20
Max. Output Current
15 Amp
16 Amp
Nominal Voltage
115V
230V
Voltage
100V~ 127V full range
200V~ 240V full range
Interface
RJ11: Ready for connecting to Cabinet Monitor
RJ45: Ethernet for connecting to PC
Frequency
50/60HZ full range
LED Indicator
Yellow LED x 1 ( SSL Indication )
Green LED x 1 ( DHCP Indication )
Red LED x 1 ( Circuit Status )
Alarm
Warning: 1 Beep per second
Overload: 3 Beeps per second
Circuit Breaker: Triggered-Continuously Beeps
Meter
3+1 Digits Meter x 1
Range: 0A~20 A (Ture RMS)
Resolution: 0.1A
Precision: +/-2%+/-0.1AMP
Additional 1 digi for POM PDU Identification