PDU (Power Distribution Units)
   
Metered PDU
   
 
Metered PDU
power_management
 
   
Introduction

The Databay Metered PDU allows an administrator to monitor PDU power consumption information from PDU panel directly. This can be helpful to check when install PDU if it has gone into a power overload state to avoid the possible power disaster.

It also can co-operate with Remote power monitoring to assistant manager can remote monitor its power consumption.

 
Features
  1. Build-in true RMS current meter.
  2. Provide audible alarm when the power consumption over the the setting of warning and overload.
  3. Provide power protection by the circuit breaker.
  4. Slim size is suitable for the variety of rack to use.
  5. emote Power Monitor Upgradeable.
 
Diagram
 


Switched PDUs Diagram

   
Specification
Interface RJ11: Ready for connecting to Remote power monitoring
Frequency 50/60Hz Full Range
LED Indicator Yellow LED x 1,Green LED x 1
Alarm Warning: 1 Beep per second
Overload: 3 Beeps per second
Circuit Breaker: Triggered-Continuously Beeps
Meter 3 Digits Meter x 1,
Range: 0A~20 A
Resolution: 0.1A
Precision: +/-2%+/-0.1AMP
Interface 0~40°C
LED Indicator -25~65°C
Operation & Environment 0 ~ 90%
   
   
Ordering Information
Model No.
Install
Input Voltage
Capacity
Ports
Input Plug
Output Socket
Breaker

PDU-GH1511-0801

1U

115V

15A
8
(1) NEMA 5-15P
(8) NEMA5-15R
1CB

PDU-GH2011-0801

1U

115V

20A
8
(1) NEMA 5-20P
(8) NEMA5-20/15R
1CB

PDU-GH2020-0801

1U

208V

20A
8
(1) NEMA L6-20P
(8) IEC320 C13
1CB
PDU-GH1623-0801
1U

230V

16A
8
(1) IEC320 C20
(8) IEC320 C13
1CB
Model No.
Description

PDU-ARPM00-08

Cabinet Monitor, For upgrade Basic PDU and Metered PDU to remote power monitoring.

PDU-ATHM00-01

Temp./Humidity Probe, Environmental and access sensors for use with remote power monitoring.
 
 

 

 

 

 

 

 

 

 

 

 

 

 

 


 

 

 


 
   